<link rel="stylesheet" href="styles.cf390c6bfbe7555f.css">

LoRaWAN-based IoT protocol for three levels central protection scheme in MT-HVDC networks with ANFIS-PSO restoration algorithm

dc.contributor.authorEladl, Abdelfattah A
dc.contributor.authorSaeed, Mohammed A
dc.contributor.authorSedhom, Bishoy E
dc.contributor.authorAbdelaziz, Almoataz Y
dc.contributor.authorBureš, Vladimír
dc.date.accessioned2025-12-05T13:57:55Z
dc.date.available2025-12-05T13:57:55Z
dc.date.issued2023
dc.description.abstractA new three-level adaptive central protection scheme has been introduced for multi-terminal high voltage direct current (MT-HVDC) transmission grids. The primary protection is based on a differential relay, while two backup protection levels are proposed: a local dv/dt under-voltage relay and a centralized overcurrent relay at the AC grid side. The coordination of these three protection levels is managed based on a convenient coordination time. The communication between the central protection unit and the Fault Isolation Devices (FIDs) is established using the LoRaWAN-based Internet of Things (IoT) protocol. In case of fault clearance triggered by the third protection level, the faulty line is detected and isolated using the adaptive neuro-fuzzy inference system (ANFIS) algorithm. The restoration process of the healthy lines focuses on minimizing load shedding and line power loss. The protection scheme proposed in this article has been implemented and tested under various fault conditions using the MATLAB/Simulink (R) environment. The results demonstrate the effectiveness and efficiency of the proposed protection scheme in detecting and isolating faulty lines in MT-HVDC transmission grids, along with a rapid restoration technique.eng
dc.formatp. 4556-4573
dc.identifier.doi10.1016/j.egyr.2023.11.013
dc.identifier.issn2352-4847
dc.identifier.obd43880666
dc.identifier.urihttp://hdl.handle.net/20.500.12603/1989
dc.identifier.wos001120910900001
dc.language.isoeng
dc.peerreviewedyes
dc.publicationstatuspostprint
dc.publisherELSEVIER
dc.relation.ispartofEnergy Reports, volume 10, issue: Novembereng
dc.relation.publisherversionhttps://www.sciencedirect.com/science/article/pii/S2352484723015378?via%3Dihub
dc.rights.accessOpen Access
dc.rights.licenseCC BY
dc.source.urlhttps://www.sciencedirect.com/science/article/pii/S2352484723015378?via%3Dihub
dc.subjectMT-HVDCeng
dc.subjectDifferential Protectioneng
dc.subjectdv / dt Protectioneng
dc.subjectRestoration Algorithmeng
dc.subjectIoTeng
dc.subjectANFISeng
dc.titleLoRaWAN-based IoT protocol for three levels central protection scheme in MT-HVDC networks with ANFIS-PSO restoration algorithmeng
dc.typearticle

Soubory

Původní svazek

Nyní se zobrazuje 1 - 1 z 1
Načítá se...
Náhled
Název:
1-s2.0-S2352484723015378-main.pdf
Velikost:
16,37 MB
Formát:
Adobe Portable Document Format